FAQ No. FAQ00722
Question
What is the voltage between the
61F Level Controller’s electrodes?
Answer
The voltage between a level electrode and common electrode is
about 7 to 8 VAC when an electrode is not submerged. When the electrodes
are submerged, the voltage drops to near 0 V due to the liquid’s specific
resistance.
There are also High-sensitivity Controllers, which have an interelectrode
voltage of 24 VAC.
Other Level Controller
FAQs
Can the K7L detect oil?
Can two 61F Controllers and two Electrode Holders be used in the same tank?
What is Interelectrode resistance?
|