FAQ No. FAQ01347
Question
What is the procedure for setting autotuning for
E8F2 Pressure Sensor?
Answer
Pressure Setting Mode
Autotuning Setting
Autotuning setting enables inputting measurement values as the settings
for the ON point and the OFF point rather than using the keys to input
values. Teaching includes one-point teaching for setting only one point
and two-point teaching for setting two points.
Note: Autotuning can be set if a is selected for the pressure setting
method for initial settings.

Setting Procedure

Note:

1. The pressure setting mode will be entered when the Set Key is pressed.
The OUT1 indicator will light and t.h1 will be displayed.
2. Use the Up and Down Keys to select 1-point or 2-point autotuning for
OUT1 and OUT2.
Two-point Autotuning (Hysteresis Mode Tuning)
OUT1

1. Press the Set Key when t.h1 is displayed at condition 1 in the
following figure to display the present measurement value.
2. Check the measurement value, press the Set Key and execute teaching to
complete teaching for the first point.
3. Press the Set Key at condition 2 in the following figure to display the
present measurement value.
Two-point Autotuning:

There is no problem if the order or size of TEACH1 and TEACH 2 are
reversed.
ON point = (TEACH1 + TEACH2) ÷ 2
OFF point = ON point − 3% F.S.
The default is 3% F.S. (variable).
4. Check the measurement value, press the Set Key and execute teaching to
complete teaching for the second point.
5. Press the Set Key for approximately 2 s when t.h1 is displayed to set
the settings using tuning and return to the measurement mode.
6. Press the Up and Down Keys at the same time to return to the
measurement mode without making the settings.
Note: The system is automatically set to hysteresis mode when two-point
teaching is performed. This setting is useful for checking vacuum contacts
and other applications.

One-point Teaching (Window Mode Teaching)

1. Press the Set Key when tw is displayed at condition 3 in the following
figure to display the present measurement value.

ON point = TEACH1 −30% F.S.
OFF point = TEACH1 +30% F.S.
The default is 10% F.S. (variable).
2. Check the measurement value, press the Set Key and execute teaching to
complete teaching.
3. Press the Set Key for approximately 2 s when tw is displayed to set the
settings using tuning and return to the measurement mode.
4. Press the Up and Down Keys at the same time to return to the
measurement mode without making the settings.
Note: The system is automatically set to window mode when one-point
teaching is performed. This setting is useful for checking source pressure
and other applications.
Teaching Errors

The setting will not be accepted when the Set Key is pressed if the PF is
outside the setting range or if the calculation result after tuning is
outside the setting range. An error display will be shown for 1 s if
tuning is performed.