Why is the operating value for the overload factor of motors and relays
given as '115% of the current setting value'?
Answer
The JEM 1357 standard for Motors and Relays states that the operating
value for the overload factor of static protective relays for motors must
be in the range of 105% to 125% of the current setting value.
The operating value of OMRON products is 115% of the current setting
value, with a ± 10% setting tolerance for the overload factor. This
combines to give a range of 105% to 125%, which satisfies the above
standard.