Frequently Asked Questions

Measuring & Monitoring Relay Topic: Overload Factor of Motors and Relays - 115% of Current Setting Value

 

FAQ No. FAQ03066

 

Question

Why is the operating value for the overload factor of motors and relays given as '115% of the current setting value'?



Answer


The JEM 1357 standard for Motors and Relays states that the operating value for the overload factor of static protective relays for motors must be in the range of 105% to 125% of the current setting value.

The operating value of OMRON products is 115% of the current setting value, with a ± 10% setting tolerance for the overload factor. This combines to give a range of 105% to 125%, which satisfies the above standard.

Applicable models: K2CM, SE Motor Protective Relay

 

 

Other Measuring & Monitoring Relay FAQs

 What does "inverse-time operation" refer to in a Motor Relay?