* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: September 24, 2012
| I/O power supply voltage | 20.4 to 26.4 VDC (24 VDC -15%/+10%) |
|---|---|
| Current consumption | 90 mA max. |
| Connection distance | Total length: 3 m Maximum length between Units: 1 m |
| Ambient operating temperature | -10°C to 55°C |
| Ambient operating humidity | 25% to 85% (with no condensation) |
| Weight | Approx. 250 g |
| Dimensions | 110 x 60 x 65 mm (W x H x D) |
| Accessories | I/O Unit Connecting Cable (40 mm) |
| Output current | 0.5 A per point max. |
|---|---|
| Residual voltage | 1.2 V max. (0.5 A DC between each output terminal and G) |
| Leakage current | 0.1 mA max. (24 VDC between each output terminal and G) |
| ON delay time | 0.5 ms max. |
| OFF delay time | 1.5 ms max. |
| Number of circuits | 2 |
| Number of counters | 1 | |
|---|---|---|
| Operating mode | Linear counter | |
| Count input | Input signal | Encoder input (A, B, Z) |
| Signal level | 24 VDC | |
| Input type | Differential phase pulse input Pulse and direction input | |
| Maximum counting speed | 50 kHz (kcps) | |
| Counting range | -8,388,608 to +8,388,607 | |
| Other | Differential phase pulse input can be set to a multiplication factor of 1 or 4. | |
| External input | Input signal | External input (IN) |
| Signal level | 24 VDC | |
| External output | Output | 2 external outputs (OUT1 and OUT2) |
| Maximum switching capacity | 24 VDC 0.5 A | |
| Allocated words | IN | 3 words |
| OUT | 3 words | |