Solid State Relays for Heaters
last update: February 9, 2026
cULus (File No.E64562) and TÜV (File No.R50124433, EN60947-4-3)
| Model | Rated voltage |
Operating voltage range |
Rated input current |
Voltage level | |
|---|---|---|---|---|---|
| Must operate voltage | Must release voltage | ||||
| G3PE-[][][]B | 12 to 24 VDC | 9.6 to 30 VDC | 7 mA max. | 9.6 VDC max. | 1.0 VDC max. |
| G3PE-[][][]BL | 15 mA max. | ||||
| Model | G3PE-
215B(L) |
G3PE-
225B(L) |
G3PE-
235B(L) |
G3PE-
245B(L) |
G3PE-
515B(L) |
G3PE-
525B(L) |
G3PE-
535B(L) |
G3PE-
545B(L) |
|---|---|---|---|---|---|---|---|---|
| Rated load
voltage |
100 to 240 VAC (50/60 Hz) | 200 to 480 VAC (50/60 Hz) | ||||||
| Load voltage
range |
75 to 264 VAC (50/60 Hz) | 180 to 528 VAC (50/60 Hz) | ||||||
| Applicable
load current * |
0.1 to 15 A
(at 40 °C) |
0.1 to 25 A
(at 40 °C) |
0.5 to 35 A
(at 25 °C) |
0.5 to 45 A
(at 25 °C) |
0.1 to 15 A
(at 40 °C) |
0.1 to 25 A
(at 40 °C) |
0.5 to 35 A
(at 25 °C) |
0.5 to 45 A
(at 25 °C) |
| Inrush current
resistance |
150 A
(60 Hz, 1 cycle) |
220 A
(60 Hz, 1 cycle) |
440 A
(60 Hz, 1 cycle) |
150 A
(60 Hz, 1 cycle) |
220 A
(60 Hz, 1 cycle) |
440 A
(60 Hz, 1 cycle) |
||
| Permissible I2t
(reference value) |
121A2s | 260A2s | 1,260A2s | 128A2s | 1,350A2s | 6,600A2s | ||
| Applicable load
(resistive load) |
3 kW
(at 200 VAC) |
5 kW
(at 200 VAC) |
7 kW
(at 200 VAC) |
9 kW
(at 200 VAC) |
6 kW
(at 400 VAC) |
10 kW
(at 400 VAC) |
14 kW
(at 400 VAC) |
18 kW
(at 400 VAC) |
| Model | G3PE
-215B |
G3PE
-225B |
G3PE
-235B |
G3PE
-245B |
G3PE
-215BL |
G3PE
-225BL |
G3PE
-235BL |
G3PE
-245BL |
|
|---|---|---|---|---|---|---|---|---|---|
| Operate time | 1/2 of load power source cycle + 1 ms max. | 1 ms max. | |||||||
| Release time | 1/2 of load power source cycle + 1 ms max. | ||||||||
| Output ON voltage drop | 1.6 V (RMS) max. | ||||||||
| Leakage current | 10 mA max. (at 200 VAC) | ||||||||
| Insulation resistance | 100 MΩ min. (at 500 VDC) | ||||||||
| Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | ||||||||
| Vibration resistance | 10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
(Mounted to DIN track) |
||||||||
| Shock resistance | Destruction: 294 m/s2 (Mounted to DIN track) | ||||||||
| Ambient storage
temperature |
- 30 to 100 °C (with no icing or condensation) | ||||||||
| Ambient operating
temperature |
- 30 to 80 °C (with no icing or condensation) | ||||||||
| Ambient operating
humidity |
45% to 85% | ||||||||
| Sealing | IP20 | ||||||||
| Weight | Approx. 240 g | Approx. 400 g | Approx. 240 g | Approx. 400 g | |||||
| SCCR
(UL508) * |
Harmonized
protection fuse |
50 kA | |||||||
| Harmonized
protection MCCB |
10 kA | ||||||||
| MTTFd (Reference value) | 1,000 years min. | ||||||||
| Model | G3PE
-515B |
G3PE
-525B |
G3PE
-535B |
G3PE
-545B |
G3PE
-515BL |
G3PE
-525BL |
G3PE
-535BL |
G3PE
-545BL |
|
|---|---|---|---|---|---|---|---|---|---|
| Operate time | 1/2 of load power source cycle + 1 ms max. | 1 ms max. | |||||||
| Release time | 1/2 of load power source cycle + 1 ms max. | ||||||||
| Output ON voltage drop | 1.8 V (RMS) max. | ||||||||
| Leakage current | 20 mA max. (at 480 VAC) | ||||||||
| Insulation resistance | 100 MΩ min. (at 500 VDC) | ||||||||
| Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | ||||||||
| Vibration resistance | 10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
(Mounted to DIN track) |
||||||||
| Shock resistance | Destruction: 294 m/s2 (Mounted to DIN track) | ||||||||
| Ambient storage
temperature |
- 30 to 100 °C (with no icing or condensation) | ||||||||
| Ambient operating
temperature |
- 30 to 80 °C (with no icing or condensation) | ||||||||
| Ambient operating
humidity |
45% to 85% | ||||||||
| Sealing | IP20 | ||||||||
| Weight | Approx. 240 g | Approx. 400 g | Approx. 240 g | Approx. 400 g | |||||
| SCCR
(UL508) * |
Harmonized
protection fuse |
50 kA | |||||||
| Harmonized
protection MCCB |
--- | 10 kA | --- | 10 kA | |||||
| MTTFd (Reference value) | 1,000 years min. | ||||||||
* Obtained through coordination with fuses and MCCB under the conditions below.
| Applicable SSR | SCCR Value | Fuse |
| G3PE-215B (L) | 50 kA | 30 A (Class CC) 600 V
60A (Class J, T, CD) 600 V 100 A (Class J) 300 V |
| G3PE-225B (L) | ||
| G3PE-235B (L) | ||
| G3PE-245B (L) | ||
| G3PE-515B (L) | 30 A (Class J, T, CC) 600 V | |
| G3PE-525B (L) | ||
| G3PE-535B (L) | 30A (Class CC) 600 V
60A (Class J, T, CD) 600 V |
|
| G3PE-545B (L) |
| Applicable SSR | SCCR Value | MCCB (UL certified) |
| G3PE-215B (L) | 10 kA | 60 A |
| G3PE-225B (L) | ||
| G3PE-235B (L) | ||
| G3PE-245B (L) | ||
| G3PE-515B (L) | ―― | |
| G3PE-525B (L) | ||
| G3PE-535B (L) | ||
| G3PE-545B (L) | 30 A |
last update: February 9, 2026