NJ/DX-Series Power Supply Unit
            
        
last update: October 1, 2025
| Item | Specifications | |
|---|---|---|
| Model | NJ-PA3001 | NJ-PD3001 | 
| Supply voltage | 100 to 240 VAC (wide-range), 50/60 Hz | 24 VDC | 
| Operating voltage and
 frequency ranges  | 
85 to 264 VAC, 47 to 63 Hz | 19.2 to 28.8 VDC | 
| Power consumption | 120 VA max. | 60 W max. | 
| Inrush current *1 | At 100 VAC: 20 A/8 ms max. for cold start at
 room temperature At 200 VAC: 40 A/8 ms max. for cold start at room temperature  | 
At 24 VDC: 30 A/20 ms max. for cold start | 
| Output capacity *2 | 5 VDC, 6.0 A (including supply to CPU Unit using CPU Rack)
 5 VDC, 6.0 A (using Expansion Rack) 24 VDC, 1.0 A Total: 30 W max.  | 
|
| Output terminal
 (service supply)  | 
Not provided | |
| RUN output *3 | Contact configuration: SPST-NO
 Switch capacity: 250 VAC, 2 A (resistive load) 120 VAC, 0.5 A (inductive load), 24 VDC, 2A (resistive load)  | 
|
| Replacement
 notification function  | 
Not provided | |
| Insulation resistance
 *4  | 
20 MΩ min. (at 500 VDC) between AC
 external and GR terminals  | 
20 MΩ min. (at 500 VDC) between DC
 external and GR terminals  | 
| Dielectric strength
 *4 *5  | 
2,300 VAC 50/60 Hz for 1 min between AC
 external and GR terminals Leakage current: 10 mA max.  | 
1,000 VAC 50/60 Hz for 1 min between DC
 external and GR terminals Leakage current: 10 mA max.  | 
| Noise immunity | 2 kV on power supply line (Conforms to IEC 61000-4-4.) | |
| Vibration resistance | 5 to 8.4 Hz, 3.5-mm amplitude, 8.4 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z directions
 for 100 min (Time coefficient: 10 min × coefficient factor 10 = total time 100 min) (according to IEC 60068-2-6)  | 
|
| Shock resistance | 147 m/s2 3 times each in X, Y, and Z directions (Relay Output Unit: 100 m/s2) (according to
 IEC 60068-2-27)  | 
|
| Ambient operating
 temperature  | 
0 to 55°C | |
| Ambient operating
 humidity  | 
10% to 90% (with no condensation) | |
| Atmosphere | Must be free from corrosive gases. | |
| Ambient storage
 temperature  | 
-20 to 75°C | |
| Grounding | Less than 100 Ω | |
| Enclosure | Mounted in panel | |
| Weight | 470 g max. | 490 g max. | 
| CPU Rack dimensions | NJ-series: 174.7 to 484.7 × 90 × 90 mm (W × D × H) (not including cables)
 W = 70 (Power Supply Unit) + 90 (CPU Unit) + 20 × n + 31 × m + 14.7 (end cover) n is the number of 32-point I/O Units or I/O Control Units and m is the number of other Units. DX-series: 148.8 × 90 × 90 (W × D × H) (not including cables) W = 70 (Power Supply Unit) + 78.8 (CPU Unit)  | 
|
| Safety measures | Conforms to cULus, EC Directives, NK, LR, RCM, and KC. | |
last update: October 1, 2025