Relay Output Units
last update: February 3, 2014
I/O power supply voltage | 20.4 to 26.4 VDC (24 VDC -15%/+10%) | |||
---|---|---|---|---|
Current consumption * | I/O Unit interface | I/O power supply | ||
GT1-ROP08 | 40 mA max. | GT1-ROP08 | 350 mA max. | |
GT1-FOP08 | GT1-FOP08 | |||
GT1-ROS16 | 50 mA max. | GT1-ROS16 | 250 mA max. | |
Connectable Units | 8 | |||
Dielectric strength | 500 VAC (between isolated circuits) | |||
Noise immunity | Conforms to IEC 61000-4-4, 2 kV (power line) | |||
Vibration resistance | 10 to 55 Hz, 1.0-mm double amplitude or 70 m/s2 | |||
Shock resistance | 200 m/s2 | |||
Mounting method | DIN 35 mm-track mounting | |||
Mounting strength | No damage when 100 N pull load was applied in all directions | |||
Terminal strength | No damage when 100 N pull load was applied | |||
Screw tightening torque | 0.3 to 0.5 Nm | |||
Ambient operating temperature | -10°C to 55°C | |||
Ambient operating humidity | 25% to 85% (with no icing or condensation) | |||
Ambient storage temperature | -25°C to 65°C | |||
Accessories | I/O Unit Connecting Cable (40 mm) |
Model | GT1-ROS16 | GT1-ROP08 | GT1-FOP08 |
---|---|---|---|
Relay model | G6D-1A-ASI (24 VDC) | G2R-1-SN (24 VDC) | G3R-ODX02SH-UTU
(5 to 24 VDC) |
Maximum contact current | 2 A | 5 A | 0.01 to 1.5 A |
Minimum applicable load
(reference values) |
5 VDC, 10 mA | 5 VDC, 100 mA | 4 to 48 VDC |
Electrical life expectancy | 100,000 operations min. with switching frequency of 1,800
operations per hour (at ambient temperature of 23°C with rated load) |
--- | |
Mechanical life expectancy | 20,000,000 operations min. with switching frequency of 18,000
operations per hour (at ambient temperature of 23°C with rated load) |
--- |
last update: February 3, 2014