Power supply voltage | 100 to 240 VAC, 50/60 Hz | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 3.5 VA | |
Sensor input | Models with thermocouple inputs
Thermocouple: K, J, T, R, or S |
|
Models with platinum resistance thermometer inputs
Platinum resistance thermometer: Pt100 |
||
Control
output |
Relay output | SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations,
minimum load: 5 V, 10 mA |
Voltage output
(for driving SSR) |
Output voltage: 12 VDC +25%/-15% (PNP), max. load current: 21 mA, with short-
circuit protection circuit |
|
Alarm output * | SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations, minimum load: 5 V, 10 mA | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Setting method | Digital setting using front panel keys | |
Indication method | 7-segment digital display and individual indicators
Character height: E5CSL: 21.7 mm, E5CWL: 16.2 mm (PV), E5EWL: 20 mm (PV) |
|
Other functions | Temperature input shift, run/stop, protection functions, etc. | |
Ambient operating temperature | -10 to 55°C (with no icing or condensation) | |
Ambient operating humidity | 25% to 85% | |
Storage temperature | -25 to 65°C (with no icing or condensation) |
* E5CWL/E5EWL only
Model
(temperature input) |
Set value | Input type | Range | |
---|---|---|---|---|
°C | °F | |||
TC input | 0 | K | -200 to 1,300 | -300 to 2,300 |
1 | -20.0 to 500.0 | 0.0 to 900.0 | ||
2 | J | -100 to 850 | -100 to 1500 | |
3 | -20.0 to 400.0 | 0.0 to 750.0 | ||
4 | T | -200 to 400 | -300 to 700 | |
5 | -199.9 to 400.0 | -199.9 to 700.0 | ||
6 | R | 0 to 1,700 | 0 to 3,000 | |
7 | S | 0 to 1,700 | 0 to 3,000 |
Default setting: 0
Applicable standards (K, J, T, R, S): JIS C1602-1995 and IEC 60584-1
Model
(temperature input) |
Set value | Input type | Range | |
---|---|---|---|---|
°C | °F | |||
Pt input | 8 | Pt100 | -200 to 850 | -300 to 1500 |
9 | -199.9 to 500.0 | -199.9 to 900.0 |
Default setting: 8
Applicable standards (Pt100): JIS C1604-1997 and IEC 60751
Select alarm types out of the 11 alarm types listed in the following table.
Setting | Alarm type | Positive alarm value (X) | Negative alarm value (X) |
---|---|---|---|
0 | No alarm | Output OFF | |
1 | Deviation upper/lower limit |
![]() |
Always ON |
2 | Deviation upper limit |
![]() |
![]() |
3 | Deviation lower limit |
![]() |
![]() |
4 | Deviation upper/lower range |
![]() |
Always OFF |
5 * | Deviation upper/lower limit standby
sequence ON |
![]() |
Always OFF |
6 * | Deviation upper limit standby
sequence ON |
![]() |
![]() |
7 * | Deviation lower limit standby
sequence ON |
![]() |
![]() |
8 | Absolute value upper limit |
![]() |
![]() |
9 | Absolute value lower limit |
![]() |
![]() |
10 * | Absolute value upper limit standby
sequence ON |
![]() |
![]() |
11 * | Absolute value lower limit standby
sequence ON |
![]() |
![]() |
12 | Do not set. |
The standby sequence is cleared when the alarm OFF condition has been met.
The standby sequence is started again when any of the following conditions is met.
Indication accuracy | Thermocouple: (See note 1.)
(±0.5% of indicated value or ±1°C, whichever is greater) ±1 digit max. Platinum resistance thermometer: (±0.5% of indicated value or ±1°C, whichever is greater) ±1 digit max. |
|
---|---|---|
Influence of temperature | R and S thermocouple inputs:
(±1% of PV or ±10°C, whichever is greater) ±1 digit max. K, J, and T thermocouple inputs: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. Platinum resistance thermometer inputs: (±1% of PV or ±2°C, whichever is greater) ±1 digit max. |
|
Influence of voltage | ||
Influence of EMS. (at EN61326-1) | ||
Hysteresis | 0.1 to 999.9 (in units of 0.1) °C/°F | |
Proportional band (P) | 0.1 to 999.9 (in units of 0.1) °C/°F | |
Integral time (I) | 0 to 3999 s (in units of 1 s) | |
Derivative time (D) | 0 to 3999 s (in units of 1 s) | |
Control period | 0.5, 1 to 99 s (in units of 1 s) | |
Alarm setting range | -1999 to 9999 (decimal point position depends on input type) | |
Sampling period | 250 ms | |
Affect of signal source resistance | Thermocouple: 0.1°C/Ω max. (100 Ω max.) (See note 2.)
Platinum resistance thermometer: 0.6°C/Ω max. (10 Ω max.) |
|
Insulation resistance | 20 MΩ min. (at 500 VDC) | |
Dielectric strength | 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) | |
Vibration resistance | Malfunction | 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions |
Destruction | 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions | |
Shock resistance | Malfunction | 100 m/s2 min., 3 times each in X, Y, and Z directions |
Destruction | 300 m/s2 min., 3 times each in X, Y, and Z directions | |
Weight | E5CSL/E5CWL | Controller: Approx. 100 g, Mounting Bracket: Approx. 10 g |
E5EWL | Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g | |
Degree of protection | Front panel: IP50
Rear case: IP20, Terminals: IP00 |
|
Memory protection | Non-volatile memory (number of writes: 100,000 times) | |
Conformed standards | EN61326-1 (See note 3.), EN61010-1, IEC61010-1
VDE0106 Part 100 (Finger protection), when the terminal cover is mounted. |
|
EMC | Emission Enclosure: EN55011 Group1 Class A
Emission AC Mains: EN55011 Group1 Class A Immunity ESD: EN61000-4-2 Immunity RF-interference: EN61000-4-3 10 V/m Immunity Conducted Disturbance: EN61000-4-6 3 V Immunity Burst: EN61000-4-4 Immunity Surge: EN61000-4-5 Immunity Voltage Dip/Interrupting: EN61000-4-11 |
Note:
1. The indication accuracy of K and T thermocouples at a temperature of −100°C max. is ±2°C ±1 digit maximum.
The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max.
2. R, and S sensors: 0.2°C/Ω max. (100 Ω max.)
3. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
last update: April 21, 2016