Slim I/O Solid State Relay
* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: January 5, 2022
Rated input
voltage |
Rated current | Must operate
voltage |
Must release
voltage |
Input voltage | ||
---|---|---|---|---|---|---|
AC | DC | Percentage of the
rated voltage |
||||
50 Hz | 60 Hz | |||||
12 VDC | - | - | 15.0 mA | 10.8 V max. | 1 V min. | ±10% |
24 VDC | - | - | 12.0 mA | 21.6 V max. | ||
24 VAC/VDC | 11.3 mA | 11.4 mA | 11.0 mA | 21.6 V max. | ||
48 VAC/VDC | 6.8 mA | 6.9 mA | 6.0 mA | 43.2 V max. | ||
100 VAC | 6.2 mA | 6.2 mA | - | 90 V max. | ||
110 VAC | 6.2 mA | 6.2 mA | - | 99 V max. | ||
200 VAC | 6.7 mA | 7.9 mA | - | 180 V max. | ||
230 VAC | 7.5 mA | 8.8 mA | - | 207 V max. |
Rated input
voltage |
Rated current | Must operate
voltage |
Must release
voltage |
Input voltage | ||
---|---|---|---|---|---|---|
AC | DC | Percentage of the
rated voltage |
||||
50 Hz | 60 Hz | |||||
12 VDC | - | - | 15.0 mA | 10.8 V max. | 1 V min. | ±10% |
24 VDC | - | - | 12.0 mA | 21.6 V max. | ||
24 VAC/VDC | 11.4 mA | 11.5 mA | 11.0 mA | 21.6 V max. | ||
48 VAC/VDC | 7.7 mA | 7.7 mA | 6.9 mA | 43.2 V max. | ||
100 VAC | 7.3 mA | 7.3 mA | - | 90 V max. | ||
110 VAC | 7.3 mA | 7.3 mA | - | 99 V max. | ||
200 VAC | 7.0 mA | 8.1 mA | - | 180 V max. | ||
230 VAC | 7.7 mA | 8.9 mA | - | 207 V max. |
Rated input
voltage |
Rated current | Must operate
voltage |
Must release
voltage |
Input voltage | ||
---|---|---|---|---|---|---|
AC | DC | Percentage of the
rated voltage |
||||
50 Hz | 60 Hz | |||||
12 VDC | - | - | 8.0 mA | 10.8 V max. | 1 V min. | ±10% |
24 VDC | - | - | 4.6 mA | 21.6 V max. | ||
24 VAC/VDC | 5.0 mA | 5.1 mA | 4.3 mA | 21.6 V max. | ||
48 VAC/VDC | 6.8 mA | 6.9 mA | 6.0 mA | 43.2 V max. | ||
100 VAC | 6.2 mA | 6.2 mA | - | 90 V max. | ||
110 VAC | 6.2 mA | 6.2 mA | - | 99 V max. | ||
200 VAC | 6.7 mA | 7.9 mA | - | 180 V max. | ||
230 VAC | 7.5 mA | 8.8 mA | - | 207 V max. |
Item | G3RV-SR700/500-A(L) | G3RV-SR700/500-D |
---|---|---|
Rated load voltage | 100 to 240 VAC (50/60 Hz) | 5 to 24 VDC |
Load voltage range | 75 to 264 VAC (50/60 Hz) | 3 to 26.4 VDC |
Load current | 0.1 to 2 A
(Ambient temperature=25°C) |
100 μA to 3 A
(Ambient temperature=25°C) |
Inrush current resistance | 30 A (10 ms) | 30 A (10 ms) |
Permissible l2t;
Joule integral value (reference value) |
15A2 s | 9 A2 s |
Applied load capacity | 400 W
(Output voltage: 200 VAC) |
72 W
(Output voltage: 24 VDC) |
Item | G3RV-SR700/500-A | G3RV-SR700/500-AL | G3RV-SR700/500-D |
---|---|---|---|
Operate time | 1/2 cycle of load
power supply +1 ms max. |
3 ms max. | 6 ms max. |
Release time | 60 ms max. | 60 ms max. | 60 ms max. |
Output ON voltage drop | 1.6 V (RMS) max. | - | |
Output ON resistance | - | 0.3 Ω max. (at 24 VDC) | |
Leaked current | 5 mA max. (at 200 VAC, 50/60 Hz) | 10 μA max. (at 24 VDC) | |
Insulation resistance | 100 MΩ min. (at 500 VDC) | ||
Dielectric strength | Between input and output 2,500 VAC 50/60 Hz 1 min | ||
Vibration resistance * | Malfunction: 10 to 55 to 10 Hz double amplitude 0.70 mm | ||
Shock resistance * | 300m/s2 | ||
Ambient operating
temperature |
Storage: -30 to +100°C (with no icing or no condensation)
Operating: -30 to +55°C (with no icing or no condensation) |
||
Ambient operating
humidity |
45 to 85% RH | ||
Weight | Approx. 38 g | ||
Pollution degree | 2 | ||
The degree of
protection by IEC60529 |
IP20 | ||
Rated impulse
dielectric strength |
4.0 kV/III | ||
Load category | LC-A | DC-12 | |
Overload current profile | 1.5Ie 1.1Ue
5s ON, 10s OFF, 10 cycles |
||
Rated insulation voltage | 240 V |
* Value when the end plate is used.
Model | Input ratings | Contact ratings |
---|---|---|
G3RV-SR700/500-D series | 12, 24 VDC
24, 48 VAC/VDC 100, 110, 200, 230 VAC |
24 VDC 3 A (resistive load) at 25°C |
G3RV-SR700/500-A(L) series | 12, 24 VDC
24, 48 VAC/DC 100, 110, 200, 230 VAC |
240 VAC 2 A (resistive load) at 25°C |
Model | Input ratings | Contact ratings |
---|---|---|
G3RV-SR700/500-D series | 12, 24 VDC
24, 48 VAC/VDC 100, 110, 200, 230 VAC |
24 VDC 3 A (resistive load) |
G3RV-SR700/500-A(L) series | 12, 24 VDC
24, 48 VAC/VDC 100, 110, 200, 230 VAC |
240 VAC 2 A (resistive load) |
last update: January 5, 2022