Manual Motor Starter (Motor Protection Circuit Breaker)
last update: November 10, 2022
Rated
current *2 In [A] |
Current
setting range Rated operating current [A] |
Instantaneo
us trip current [A] |
3-phase standard motor capacity
and full load current *1 |
Model | Rated breaking
current Icu [kA] |
|||||
---|---|---|---|---|---|---|---|---|---|---|
200-240 VAC | 380-440 VAC | |||||||||
Capacity
[kW] |
Current
[A] |
Capacity
[kW] |
Current
[A] |
240
VAC |
415
VAC |
440
VAC |
||||
0.16 | 0.1 to 0.16 | 2.1 | --- | --- | 0.02 | 0.1 | J7MC-3P-E16 | 100 | 100 | 100 |
0.25 | 0.16 to 0.25 | 3.3 | 0.03 | 0.24 | 0.06 | 0.21 | J7MC-3P-E25 | |||
0.4 | 0.25 to 0.4 | 5.2 | 0.06 | 0.37 | 0.1 | 0.34 | J7MC-3P-E4 | |||
0.63 | 0.4 to 0.63 | 8.2 | --- | --- | 0.12 | 0.41 | J7MC-3P-E63 | |||
1 | 0.63 to 1 | 13 | 0.1 | 0.68 | 0.2 | 0.65 | J7MC-3P-1 | |||
1.6 | 1 to 1.6 | 20.8 | 0.2 | 1.3 | 0.4 | 1.15 | J7MC-3P-1E6 | |||
2.5 | 1.6 to 2.5 | 32.5 | 0.4 | 2.3 | 0.75 | 1.8 | J7MC-3P-2E5 | |||
4 | 2.5 to 4 | 52 | 0.75 | 3.5 | 1.5 | 3.5 | J7MC-3P-4 | |||
6.3 | 4 to 6.3 | 81.9 | --- | --- | 2.2 | 4.8 | J7MC-3P-6 | 50 | ||
10 | 6.3 to 10 | 130 | 1.5 | 6.9 | 3.7 | 7.8 | J7MC-3P-10 | 15 | ||
2.2 | 9.5 | |||||||||
13 | 9 to 13 | 169 | 2.2 | 9.5 | 5.5 | 10.5 | J7MC-3P-13 | 50 | 10 | |
16 | 11 to 16 | 208 | 3.7 | 15.5 | 7.5 | 13.5 | J7MC-3P-16 | 25 | ||
20 | 14 to 20 | 260 | 3.7 | 15.5 | 11 | 20 | J7MC-3P-20 | 50 |
Rated
current *2 In [A] |
Current
setting range Rated operating current [A] |
Instantaneo
us trip current [A] |
3-phase standard motor capacity
and full load current *1 |
Model | Rated breaking
current Icu [kA] |
|||||
---|---|---|---|---|---|---|---|---|---|---|
200-240 VAC | 380-440 VAC | |||||||||
Capacity
[kW] |
Current
[A] |
Capacity
[kW] |
Current
[A] |
240
VAC |
415
VAC |
440
VAC |
||||
0.16 | 0.1 to 0.16 | 2.1 | --- | --- | 0.02 | 0.1 | J7MC-3R-E16 | 100 | 100 | 100 |
0.25 | 0.16 to 0.25 | 3.3 | 0.03 | 0.24 | 0.06 | 0.21 | J7MC-3R-E25 | |||
0.4 | 0.25 to 0.4 | 5.2 | 0.06 | 0.37 | 0.1 | 0.34 | J7MC-3R-E4 | |||
0.63 | 0.4 to 0.63 | 8.2 | --- | --- | 0.12 | 0.41 | J7MC-3R-E63 | |||
1 | 0.63 to 1 | 13 | 0.1 | 0.68 | 0.2 | 0.65 | J7MC-3R-1 | |||
1.6 | 1 to 1.6 | 20.8 | 0.2 | 1.3 | 0.4 | 1.15 | J7MC-3R-1E6 | |||
2.5 | 1.6 to 2.5 | 32.5 | 0.4 | 2.3 | 0.75 | 1.8 | J7MC-3R-2E5 | |||
4 | 2.5 to 4 | 52 | 0.75 | 3.5 | 1.5 | 3.5 | J7MC-3R-4 | |||
6.3 | 4 to 6.3 | 81.9 | --- | --- | 2.2 | 4.8 | J7MC-3R-6 | |||
10 | 6.3 to 10 | 130 | 1.5 | 6.9 | 3.7 | 7.8 | J7MC-3R-10 | 50 | ||
2.2 | 9.5 | |||||||||
13 | 9 to 13 | 169 | 2.2 | 9.5 | 5.5 | 10.5 | J7MC-3R-13 | |||
16 | 11 to 16 | 208 | 3.7 | 15.5 | 7.5 | 13.5 | J7MC-3R-16 | 50 | 35 *3 | |
20 | 14 to 20 | 260 | 3.7 | 15.5 | 11 | 20 | J7MC-3R-20 |
*1. Full load currents are values for 200 VAC / 50 Hz, 400 VAC / 50 Hz, 4P reference motors.
Before applying them, check the full load current of the motor used.
*2. Maximum thermal current setting value
*3. JEM1195 breaking duty "O", single time breaking capacity is 50 kA.
Model | J7MC-3P-[] (standard type) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Item | |||||||||||||
Switch type | Rocker switch | ||||||||||||
Number of poles | 3 | ||||||||||||
Rated current In | 0.16 to 20 A | ||||||||||||
Rated operational voltage Ue | 200 to 690 V | ||||||||||||
Rated frequency | 50/60 Hz | ||||||||||||
Rated insulation voltage | 690VAC | ||||||||||||
Rated impulse dielectric strength | 6 kV | ||||||||||||
Use category | IEC 60947-2
(circuit breaker), JIS C 8201-2 |
Cat.A | |||||||||||
IEC 60947-4-1
(motor starter), JIS C 8201-4-1 |
AC-3 | ||||||||||||
Trip class
(IEC 60947-4-1/JIS C 8201-4-1) |
10 Trips within 4 minutes at 150% Ie on hot start,
trips in 4 to 10 seconds at 720% Ie on cold start |
||||||||||||
Instantaneous trip characteristics | 13 x Ie max. | ||||||||||||
Power loss (3-phase reference value) | Rated current 0.16 to 2.5 A: 6 W
Rated current 4 to 6.3 A: 6.5 W Rated current 10 to 20 A: 7 W |
||||||||||||
Endurance | Mechanical | 100,000 cycles In=0.16 to 20 A | |||||||||||
Electrical | 100,000 cycles In=0.16 to 20 A | ||||||||||||
Number of terminal insertions
and removals [cycles] |
20 | ||||||||||||
Maximum operate frequency
(motor starts) [cycles/hour] |
25 | ||||||||||||
Phase failure protection | Yes | ||||||||||||
Trip indicator | Yes | ||||||||||||
Test trip function | Yes | ||||||||||||
Rated limit breaking
capacity Icu: Rated limit breaking capacity [kA] (Breaking duty O-CO) Ics: Rated operating breaking capacity [kA] (Breaking duty O-CO-CO) Ics=100%Icu (Icu=100 kA |
Rated
operational current Ie Current setting [A] |
IEC 60947-2/JIS C 8201-2 | UL | ||||||||||
240 V
200 V |
415 V
400 V |
460 V
440 V |
500 V | 690 V
600 V |
480 V | ||||||||
Icu | Ics | Icu | Ics | Icu | Ics | Icu | Ics | Icu | Ics | Icu | Ics | ||
0.1-0.16 | 100 | 100 | 100 | 100 | 100 | 50 | |||||||
0.16-0.25 | 100 | 100 | 100 | 100 | 100 | 50 | |||||||
0.25-0.4 | 100 | 100 | 100 | 100 | 100 | 50 | |||||||
0.4-0.63 | 100 | 100 | 100 | 100 | 100 | 50 | |||||||
0.63-1 | 100 | 100 | 100 | 100 | 100 | 50 | |||||||
1-1.6 | 100 | 100 | 100 | 100 | 100 | 50 | |||||||
1.6-2.5 | 100 | 100 | 100 | 100 | 3 | 2 | 50 | ||||||
2.5-4 | 100 | 100 | 100 | 100 | 3 | 2 | 50 | ||||||
4-6.3 | 100 | 100 | 50 | 38 | 50 | 38 | 3 | 2 | 22 | ||||
6.3-10 | 100 | 100 | 15 | 11 | 10 | 8 | 3 | 2 | 22 | ||||
9-13 | 100 | 50 | 38 | 10 | 8 | 6 | 5 | 3 | 2 | 22 | |||
11-16 | 100 | 25 | 19 | 10 | 8 | 6 | 5 | 3 | 2 | 22 | |||
14-20 | 50 | 38 | 25 | 19 | 10 | 8 | 6 | 5 | 3 | 2 | 22 | ||
Vibration resistance | Vibration: 10 to 55 Hz, acceleration: 15 m/s2 | ||||||||||||
Shock resistance | Shock value 50 m/s2 | ||||||||||||
Degree of protection | IP20 (IEC60529) | ||||||||||||
Operating temperature | -20°C to +60°C | ||||||||||||
Ambient storage temperature | -40°C to +80°C (no condensation or icing) | ||||||||||||
Relative humidity | 95% RH max. (no condensation or icing) | ||||||||||||
Altitude | 2000m max. | ||||||||||||
Weight | Approx. 430 g | ||||||||||||
Applicable Standards | Safety
Standard |
EN 60947-2 (IEC 60947-2, IEC 60947-4-1),
UL60947-4-1, CSA 22.2 No.60947-4-1, CCC GB/T 14048.2, GB/T 14048.4, Electrical Appliances and Material Safety Act (Non-Specified Electrical Appliances and Materials), UKCA |
Model | J7MC-3R-[] (high-performance type) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Item | |||||||||||||
Switch type | Rotary switch | ||||||||||||
Number of poles | 3 | ||||||||||||
Rated current In | 0.16 to 20 A | ||||||||||||
Rated operational voltage Ue | 200 to 690 V | ||||||||||||
Rated frequency | 50/60 Hz | ||||||||||||
Rated insulation voltage | 690VAC | ||||||||||||
Rated impulse dielectric strength | 6 kV | ||||||||||||
Use category | IEC 60947-2
(circuit breaker), JIS C 8201-2 |
Cat.A | |||||||||||
IEC 60947-4-1
(motor starter), JIS C 8201-4-1 |
AC-3 | ||||||||||||
Trip class
(IEC 60947-4-1/JIS C 8201-4-1) |
10 Trips within 4 minutes at 150% Ie on hot start,
trips in 4 to 10 seconds at 720% Ie on cold start |
||||||||||||
Instantaneous trip characteristics | 13 x Ie max. | ||||||||||||
Power loss (3-phase reference value) | Rated current 0.16 to 1.6 A: 6 W
Rated current 2.5 to 4 A: 6.5 W Rated current 6.3 to 20 A: 7 W |
||||||||||||
Endurance | Mechanical | 100,000 cycles In=0.16 to 20 A | |||||||||||
Electrical | 100,000 cycles In=0.16 to 20 A | ||||||||||||
Number of terminal insertions
and removals [cycles] |
20 | ||||||||||||
Maximum operate frequency
(motor starts) [cycles/hour] |
25 | ||||||||||||
Phase failure protection | Yes | ||||||||||||
Trip indicator | Yes | ||||||||||||
Test trip function | Yes | ||||||||||||
Rated limit breaking
capacity Icu: Rated limit breaking capacity [kA] (Breaking duty O-CO) Ics: Rated operating breaking capacity [kA] (Breaking duty O-CO-CO) Ics=100%Icu (Icu=100 kA |
Rated
operational current Ie Current setting [A] |
IEC 60947-2/JIS C 8201-2 | UL | ||||||||||
240 V
200 V |
415 V
400 V |
460 V
440 V |
500 V | 690 V
600 V |
480 V | ||||||||
Icu | Ics | Icu | Ics | Icu | Ics | Icu | Ics | Icu | Ics | Icu | Ics | ||
0.1-0.16 | 100 | 100 | 100 | 100 | 100 | 50 | |||||||
0.16-0.25 | 100 | 100 | 100 | 100 | 100 | 50 | |||||||
0.25-0.4 | 100 | 100 | 100 | 100 | 100 | 50 | |||||||
0.4-0.63 | 100 | 100 | 100 | 100 | 100 | 50 | |||||||
0.63-1 | 100 | 100 | 100 | 100 | 100 | 50 | |||||||
1-1.6 | 100 | 100 | 100 | 100 | 100 | 50 | |||||||
1.6-2.5 | 100 | 100 | 100 | 100 | 8 | 6 | 50 | ||||||
2.5-4 | 100 | 100 | 100 | 100 | 8 | 6 | 50 | ||||||
4-6.3 | 100 | 100 | 100 | 100 | 6 | 5 | 50 | ||||||
6.3-10 | 100 | 100 | 50 | 38 | 50 | 38 | 6 | 5 | 50 | ||||
9-13 | 100 | 100 | 50 | 38 | 42 | 32 | 6 | 5 | 50 | ||||
11-16 | 100 | 50 | 38 | 35
* |
27 | 10 | 8 | 4 | 3 | 50 | |||
14-20 | 100 | 50 | 38 | 35
* |
27 | 10 | 8 | 4 | 3 | 50 | |||
Vibration resistance | Vibration: 10 to 55 Hz, acceleration: 15 m/s2 | ||||||||||||
Shock resistance | Shock value 50 m/s2 | ||||||||||||
Degree of protection | IP20 (IEC60529) | ||||||||||||
Operating temperature | -20°C to +60°C | ||||||||||||
Ambient storage temperature | -40°C to +80°C (no condensation or icing) | ||||||||||||
Relative humidity | 95% RH max. (no condensation or icing) | ||||||||||||
Altitude | 2000m max. | ||||||||||||
Weight | 460 g | ||||||||||||
Applicable Standards | Safety
Standard |
EN 60947-2 (IEC 60947-2, IEC 60947-4-1),
UL60947-4-1, CSA 22.2 No.60947-4-1, CCC GB/T 14048.2, GB/T 14048.4, Electrical Appliances and Material Safety Act (Non-Specified Electrical Appliances and Materials), UKCA |
* JEM1195 breaking duty "O", single time breaking capacity is 50 kA
Model | J73MC-W-[] | J73MC-K-[] | ||||
---|---|---|---|---|---|---|
Compliant standards | IEC 60947-5-1, UL 508 | |||||
Auxiliary contact | SPST-1NO (1a), SPST-1NC (1b) | |||||
Rated carry current [A] | IEC 60947-5-1 | 6 | ||||
UL 508 | 5 | |||||
Rated
operating current [A] |
IEC 60947-5-1 | AC-15 | 48 V | 5 | ||
125 V | 3 | |||||
230 V | 1.5 | |||||
DC-13 | 48 V | 1.38 | ||||
110 V | 0.55 | |||||
220 V | 0.27 | |||||
UL 508 | AC | B300 | 120 V | 3 | ||
240 V | 1.5 | |||||
DC | Q300 | 125 V | 0.55 | |||
250 V | 0.27 | |||||
Mechanical life expectancy [cycles] | 100,000 | 1,000 | ||||
Minimum operating voltage/current | 17 VDC, 5 mA | |||||
Contact form | Double-break | |||||
Contact material | Ag alloy |