Solid-state Timer
last update: May 27, 2024
Item | H3BA-N | H3BA-N8H |
---|---|---|
Operating mode | A: ON-delay
B: Flicker OFF start B2: Flicker ON start C: Signal ON/OFF-delay D: Signal OFF-delay E: Interval G: Signal ON/OFF-delay J: One-shot |
A: ON-delay
H: ON-delay with instantaneous output contact |
Pin type | 11-pin | 8-pin |
Input type | No-voltage input | --- |
Output type | DPDT (time-limit) | SPDT (time-limit) and switchable SPDT (time-limit <--->
instantaneous) |
Mounting method | DIN track mounting, surface mounting, and flush mounting | |
Approved standards | UL508 *1, CSA C22.2 No.14, LR, CCC: GB/T 14048.5 *2
Conforms to EN61812-1 (Pollution degree 2/Overvoltage category III) |
|
EMC | (EMI) EN61812-1
Radiated Emissions: EN 55011 class A Emission AC Mains: EN 55011 class A (EMS) EN61812-1 ESD Immunity: EN 61000-4-2: 6 kV contact discharge, 8 kV air discharge Radiated Radio-Frequency EN 61000-4-3: 10 V/m (80 MHz to 1 GHz AM modulation) Electromagnetic Field Immunity: 3 V/m (1.4 GHz to 2 GHz AM modulation), 1 V/m (2 GHz to 2.7 GHz AM modulation), 10 V/m (900 MHz Pulse modulation) Conducted disturbances: EN 61000-4-6: 10 V (0.15 MHz to 80 MHz) Burst Immunity: EN 61000-4-4: 2 kV power line, 2 kV I/O signal line Surge Immunity: EN 61000-4-5: 2 kV common mode, 1 kV differential mode Voltage dips: EN 61000-4-11 Voltage interruptions: EN 61000-4-11 |
Recommended fuse | 0216005 (250 VAC, 5 A) manufactured by Littelfuse |
---|---|
Rated operating voltage Ue
Rated operating current Ie |
AC-15: Ue: 250 VAC, Ie: 3 A
AC-13: Ue: 250 VAC, Ie: 5 A DC-13: Ue: 30 VDC, Ie: 1.5 A |
Rated insulation voltage | 250 V |
Rated impulse withstand voltage
(altitude: 2,000 m max.) |
4 kV (at 240 VAC) |
Conditional short-circuit current | 1,000 A |
Time unit | sec | × 10 s | min | × 10 m | hrs | × 10 h | |
---|---|---|---|---|---|---|---|
Full scale setting | |||||||
1.2 | Set time | 0.05 to 1.2 | 1.2 to 12 | 0.12 to 1.2 | 1.2 to 12 | 0.12 to 1.2 | 1.2 to 12 |
3 | 0.3 to 3 | 3 to 30 | 0.3 to 3 | 3 to 30 | 0.3 to 3 | 3 to 30 | |
12 | 1.2 to 12 | 12 to 120 | 1.2 to 12 | 12 to 120 | 1.2 to 12 | 12 to 120 | |
30 | 3 to 30 | 30 to 300 | 3 to 30 | 30 to 300 | 3 to 30 | 30 to 300 |
Item | H3BA-N | H3BA-N8H |
---|---|---|
Rated supply voltage *1 *2 | 110 VAC (50/60 Hz), 220 VAC (50/60 Hz), 24 VDC | |
Operating voltage range *3 | 85% to 110% of rated supply voltage | |
Power reset | Minimum power-opening time: 0.1 s | |
No-voltage input | ON impedance: 1 kΩ max.
ON residual voltage: 1 V max. OFF impedance: 200 kΩ min. |
|
Power consumption | 110 VAC: Approx. 4.6 VA (1.5 W)
220 VAC: Approx. 7.6 VA (1.3 W) 24 VDC: Approx. 0.6 W |
110 VAC: Approx. 3.6 VA (1.6 W)
220 VAC: Approx. 7.8 VA (1.9 W) 24 VDC: Approx. 0.9 W |
Control outputs | Contact: 5 A at 250 VAC, resistance load (cosφ = 1) |
Item | H3BA-N | H3BA-N8H |
---|---|---|
Accuracy of operating time | ±0.3% FS max. (±0.3%±10 ms in a range of 1.2 s) | |
Setting error | ±5% FS ±0.05 s max. | |
Reset time | Min. power-opening time: 0.1 s max.
Min. pulse-input time: 50 ms |
|
Influence of voltage | ±0.5% FS max. (±0.5%±10 ms in a range of 1.2 s) | |
Influence of temperature | ±2% FS max. (±2%±10 ms in a range of 1.2 s) | |
Insulation resistance | 100 MΩ min. (at 500 VDC) | |
Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and exposed non-
current-carrying metal parts 2,000 VAC, 50/60 Hz for 1 min between control output terminals and operating circuit 1,000 VAC, 50/60 Hz for 1 min between contacts not located next to each other (750 VAC for H3BA-N8H) |
|
Impulse withstand voltage | 1 kV (between power terminals)
2 kV (between current-carrying terminal and exposed non-current-carrying metal parts, 1.5 kV for 24-VDC models) |
|
Noise immunity | AC models:
±1.5 kV (between power terminals), and ±600 V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) DC models: ±480 V (between power terminals), and ±600 V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) |
|
Static immunity | Malfunction: 4 kV
Destruction: 8 kV |
|
Vibration resistance | Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude each in three directions |
|
Shock resistance | Destruction: 1,000 m/s2 (approx. 100G) each in three directions
Malfunction: 100 m/s2 (approx. 10G) each in three directions |
|
Ambient temperature | Operating: -10°C to 55°C (with no icing)
Storage: -25°C to 65°C (with no icing) |
|
Ambient humidity | Operating: 35% to 85% | |
Life expectancy | Mechanical: 10 million operations min.
(under no load at 1,800 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) |
Mechanical: 10 million operations min.
(under no load at 1,800 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h) |
Case color | Light gray (Munsell 5Y7/1) | |
Enclosure ratings | IEC: IP40 (panel surface) | |
Weight | Approx. 95 g |
last update: May 27, 2024